V1.496-Zone Expandable Security and Access Control PanelReference and Installation ManualDGP-NE96www.paradox.ca
8 REFERENCE & INSTALLATION MANUALFigure 2-6: Single Zone Input Connections2.14 DOUBLE ZONE CONNECTIONSEnabling the ATZ feature (see section 4.2) a
DIGIPLEXNE CONTROL PANEL 92.16 COMBUS CONNECTIONSModules can connect anywhere on the 4-wire combus, which can support up to 127 modules. Connect in
10 REFERENCE & INSTALLATION MANUALFor TBR-21 compliance, please note the following:1) The DGP-NE96 can be connected to the telephone network via a
DIGIPLEXNE CONTROL PANEL 113 PROGRAMMING METHODSDigiplexNE can be programmed using the following methods:3.1 WINLOAD UPLOADING/DOWNLOADING SOFTWARE
12 REFERENCE & INSTALLATION MANUAL4 ZONE PROGRAMMINGAll detection devices connected to the control panel, keypads and zone expansion modules must
DIGIPLEXNE CONTROL PANEL 134.1.1 Clearing a Zone’s NumberingFor LCD Keypads:1) Enter a section number between [0001] to [0096].2) Press [0] and then
14 REFERENCE & INSTALLATION MANUAL4.3.10 24Hr Water Zones*SECTIONS [0101] TO [0196]: FIRST DIGIT = AWhen a 24Hr Water zone opens, whether it is ar
DIGIPLEXNE CONTROL PANEL 154.5.3 Stay ZonesSECTIONS [0101] TO [0196]: OPTION [3]Only zones with option [3] enabled will be bypassed when the partiti
16 REFERENCE & INSTALLATION MANUAL5 KEYSWITCH PROGRAMMINGThe DigiplexNE control panel can support up to 32 keyswitch zones in addition to the 96
DIGIPLEXNE CONTROL PANEL 175.2.4 Generates a Utility Key Event on OpenSECTIONS [0601] TO [0632]: FIRST DIGIT = 3When option [3] is enabled, a Utilit
18 REFERENCE & INSTALLATION MANUAL6 ARMING AND DISARMING OPTIONS6.1 ARMING FOLLOWS PARTITION(Default = disabled) A partition can be set to follow
DIGIPLEXNE CONTROL PANEL 196.9.1 Auto-Arm TimerWhen Timed Auto-Arming is enabled (see section 6.9), the control panel will attempt to arm the system
20 REFERENCE & INSTALLATION MANUALFigure 6-1: Example of Exit Delay TerminationEnable option [4] in the desired section: 6.16.2 No Exit Delay on R
DIGIPLEXNE CONTROL PANEL 217 ALARM OPTIONS7.1 BELL/ALARM OUTPUT(Default = only option [1] enabled) When an alarm condition is detected in a partiti
22 REFERENCE & INSTALLATION MANUAL7.5.1 Tamper Bypass OptionsSECTION [3034]: OPTION [7] (Default = enabled) With option [7] enabled in section [30
DIGIPLEXNE CONTROL PANEL 238 EVENT REPORTINGFigure 8-1: Event ReportingDialing Enabled/DisabledSection [3036]Option [3]Reporting Account NumbersCen
24 REFERENCE & INSTALLATION MANUAL8.1 REPORTING ENABLEDSECTION [3036]: OPTION [3] (Default = disabled) With option [3] ON in section [3036], Event
DIGIPLEXNE CONTROL PANEL 258.2.9 Special Disarming Report CodesWhen using one of the special disarming features listed below, the control panel can
26 REFERENCE & INSTALLATION MANUALClose [3916], Late to Close [3917], Early to Open [3926] or Late to Open [3927]. In the desired section enable o
DIGIPLEXNE CONTROL PANEL 271, the control panel will send the Partition 1 Account Number defined in section [3061] followed by the report code.Only
DIGIPLEXNE CONTROL PANEL 1TABLE OF CONTENTSINTRODUCTION ... 3Features...
28 REFERENCE & INSTALLATION MANUAL8.8.1 Maximum Dialing Attempts**SECTION [3056](Default = 008) The number (001 to 255, 000 = 8 attempts) programm
DIGIPLEXNE CONTROL PANEL 298.16 CLOSING DELINQUENCY TIMER(Default = 000; Disabled) When a partition in the system is disarmed, the control panel wil
30 REFERENCE & INSTALLATION MANUAL9 DIALER OPTIONS9.1 TELEPHONE LINE MONITORINGSECTION [3036]: OPTIONS [1] AND [2]When enabled, the system verifi
DIGIPLEXNE CONTROL PANEL 3110 PROGRAMMABLE OUTPUTSA PGM is a programmable output that toggles to its opposite state (i.e. a normally open PGM will
32 REFERENCE & INSTALLATION MANUAL11 SYSTEM SETTINGS AND COMMANDS11.1 HARDWARE RESETA Hardware Reset sets sections [0001] to [3991] to default, i
DIGIPLEXNE CONTROL PANEL 33Delay, Bell Squawk, One-touch Arming, Panic Alarms and many more. All zones, keyswitch zones, user codes and system modul
34 REFERENCE & INSTALLATION MANUAL11.17 CLOCK COMPENSATION VALUESECTION [3050](Default = Disabled) When the DigiplexNE’s clock is inaccurate, a cl
DIGIPLEXNE CONTROL PANEL 35Table 8: Special Characters Catalogue Table 9: Hebrew Keypad Letter AssignmentTable 10: Russian Keypad Letter AssignmentT
36 REFERENCE & INSTALLATION MANUAL12 ACCESS CODES12.1 INSTALLER CODE SECTION [1000](Default: 000000) The Installer Code is used to enter the cont
DIGIPLEXNE CONTROL PANEL 3712.6 PARTITION ASSIGNMENTSECTIONS [1002] TO [1999]: ASSIGN AREA SCREEN, OPTIONS [1] TO [8] Each of the 998 User Access Co
2 REFERENCE & INSTALLATION MANUALDaylight Savings Time... 32Battery Charge Current...
38 REFERENCE & INSTALLATION MANUAL13 ACCESS CONTROL: SYSTEM FEATURESAccess Control defines the days and times people are allowed to enter and exi
DIGIPLEXNE CONTROL PANEL 39Start Time and End Time during the holidays. An Interval cannot cross into another day (overnight). Schedules are assigne
40 REFERENCE & INSTALLATION MANUALWhen option [3] is enabled, the Access Card must be presented before the User Access Code is entered.13.13 SKIP
DIGIPLEXNE CONTROL PANEL 4114 WINLOAD SOFTWARE14.1 PANEL IDENTIFIERSECTION [3011](Default = 0000) The Panel Identifier identifies the control panel
42 REFERENCE & INSTALLATION MANUAL15 USER FEATURES15.1 REGULAR ARMINGThis method is used for the everyday arming of the system. All zones within
DIGIPLEXNE CONTROL PANEL 432) Using the scroll keys, highlight Bypass and then press the center action key (Ok).3) Highlight the zone that you wish
44 REFERENCE & INSTALLATION MANUALStep 3: If more than one Trouble Group appears, highlight the desired group before pressing the center action ke
DIGIPLEXNE CONTROL PANEL 4516 APPENDIX 1: PGM PROGRAMMING TABLEEvent Group Event Feature Group Feature Start # End #000 Zone is OK000255 = any Zone
46 REFERENCE & INSTALLATION MANUAL012 Special Arming (cont’d)000No Movement Arming 003 003Partial Arming 004 004One-touch Arming 005 005Future Use
DIGIPLEXNE CONTROL PANEL 47022 Special Disarming (cont’d)000 (InTouch) Voice Module Disarming 008 008255 Any Special Disarming Event Not Used Not Us
DIGIPLEXNE CONTROL PANEL 31 INTRODUCTIONDigiplexNE is a security and access control system with 8 on-board zone inputs (16 with zone doubling) that
48 REFERENCE & INSTALLATION MANUAL038 Module Trouble000Combus Fault 000 000Module Tamper 001 001ROM/RAM error 002 002TLM Trouble 003 003Fail to Co
DIGIPLEXNE CONTROL PANEL 49054 Door Forced Open Restore000255 = any Door NumberDoor Numbers 001 to 032 001 to 032055 Intellizone Triggered000 Zone
50 REFERENCE & INSTALLATION MANUALNOTE 1:NOTE 2: This TLM trouble event can only be used with the DigiplexNE control panel models that have two di
DIGIPLEXNE CONTROL PANEL 51†:** Keyswitch‡ Refer to the Omnia™ Reference and Installation Manual for remote control button programming instructions.
52 REFERENCE & INSTALLATION MANUAL17 APPENDIX 2: AUTOMATIC REPORT CODE LISTSystem EventDefault Contact ID Report Codefor sections [4032] to [4037
DIGIPLEXNE CONTROL PANEL 53AC Failure restore 3 3A1 - AC loss restore AR - AC RestoralBattery Failure restore 3 3A9 - Battery test restore YR - Syst
54 REFERENCE & INSTALLATION MANUAL18 APPENDIX 3: CONTACT ID REPORT CODE LISTCID# Reporting CodeProg.ValueCID# Reporting CodeProg.ValueCID# Report
DIGIPLEXNE CONTROL PANEL 5519 INDEXSectionsAAC Failure not Displayed ... 34AC Power ...
56 REFERENCE & INSTALLATION MANUALCode Follows Schedule ... 37CodesSpecial Alarm Report Codes
DIGIPLEXNE CONTROL PANEL 57Keypad Beep on Successful Arm/Disarm Report ... 30Keypad Lockout ...
4 REFERENCE & INSTALLATION MANUAL2 INSTALLATION2.1 RECOMMENDED INSTALLATION PROCEDUREIn order to facilitate installation, we recommend connectin
58 REFERENCE & INSTALLATION MANUALSSchedule Assignment ... 37Schedule Tolerance Window ...
DIGIPLEXNE CONTROL PANEL 5920 WARNINGSFCC WarningsIMPORTANT INFORMATIONThis equipment complies with Part 68 of the FCC rules subpart D and CS-03. I
60 REFERENCE & INSTALLATION MANUALGrade B Central Station (Level 0)Same as Household Grade A Burglar alarm system unit except:• The ringback featu
Printed in Canada - 01/2004 DGPNE96-EI07
DIGIPLEXNE CONTROL PANEL 5Figure 2-3: DigiplexNE Control Panel Wiring DiagramWhen installing the combus wires in a noisy environment, or when connecti
6 REFERENCE & INSTALLATION MANUAL2.11 CALCULATING POWER REQUIREMENTSSTEP 1: Using Table 1, calculate the total number of power units (PU) required
DIGIPLEXNE CONTROL PANEL 7Figure 2-4: Sample Power Requirement Calculations An LCD Keypad (80PU) can be added to the 100ft. or 300ft. wire in Figure