EVO Control Panel 47
3.5.11 Beep on Trouble
SECTION [005]: OPTIONS [1] TO [4]
O
ption [1] OFF=Beep disabled: System Troubles and Clock Loss
Option [1] ON=Beep enabled: System Troubles and Clock Loss
Option [2] OFF=Beep disabled: Communicator Troubles
Option [2] ON=Beep enabled: Communicator Troubles
Option [3] OFF=Beep disabled: Module and Combus Troubles
Option [3] ON=Beep enabled: Module and Combus Troubles
Option [4] OFF=Beep disabled: all Zone Troubles
Option [4] ON=Beep enabled: all Zone Troubles
3.5.12 Keypad Tamper Enable
SECTION [006]: OPTION [5]
Option [5] OFF=Keypad's tamper is disabled (default)
Option [5] ON=Keypad's tamper is enabled
3.5.13 Time Format
SECTION [005]: OPTION [7]
Option [7] OFF=Time uses the International time format (default).
Option [7] ON=Time uses the US time format.
3.5.14 Combus Voltmeter
1. From Normal Mode press and hold the [0] key.
2. Enter the [
INSTALLER CODE] (by default 000000).
3. Press [ACC].
The voltage may drop during the control panel battery test.
3.6 Access Control Options
3.6.1 Assigning Doors To Partitions
SECTION [002]: OPTIONS [1] TO [8]
The Access Control door can be assigned to one or more partition(s) in the
alarm system. This means that the actions performed with the Access
Control Card will be directly linked to the partition(s) assigned to that door.
Option [1] ON =Door assigned to Partition 1(default)
Option [2] ON =Door assigned to Partition 2
Option [3] ON=Door assigned to Partition 3
Option [4] ON =Door assigned to Partition 4
Option [5] ON=Door assigned to Partition 5
Option [6] ON=Door assigned to Partition 6
Option [7] ON=Door assigned to Partition 7
Option [8] ON=Door assigned to Partition 8
OFF = Access Control Cards will not be able to arm and/or disarm
partitions from the door's reader
3.6.2 Unlock on REX (Request For Exit)
SECTION [006]: OPTION [8]
Option [8] OFF=Unlock on REX disabled (default)
Option [8] ON=Unlock on REX enabled
3.6.3 Door Unlocked Period
SECTION [008]
Enter any value between 001 and 255 to determine the seconds the door
can remain unlocked. Default = 5 secs.
3.6.4 Door Unlocked Period Extension
SECTION [009]
The Door Unlocked Period Extension is the amount of time added to the
Door Unlocked Period in section [008], which leaves the door unlocked
longer. This will allow those with this feature enabled on their User Access
Codes extra time to enter. Enter any value between 001 and 255 to
determine the number of seconds to be added to the time programmed in
section [008]. Default = 15 secs.
3.6.5 Relock Door
SECTION [006]: OPTION [6]
Option [6] OFF=Locking device latches immediately (default)
Option [6] ON=Locking device latches when door closes
3.6.6 Door Unlocked Schedule
SECTION [017]
The Door Unlocked Schedule determines the hours, days, and holidays
that the door will remain unlocked. Program the Start Time and End Time
according to the 24-hour clock within the same day. Use Feature Select
Programming to set the options representing the Days.
3.6.7 Card Activates Door Unlocked Schedule
SECTION [006]: OPTION [1]
Option [1] OFF=The Schedule activates without Card
Option [1] ON=Card activates Door Unlocked Schedule (default)
3.6.8 Door Left Open Access Alarm
SECTION [006]: OPTION [2]
Option [2] OFF=Door Left Open Alarm won’t be generated (default)
Option [2] ON=Door Left Open Alarm is enabled
3.6.9 Door Left Open Interval Before Access Alarm
SECTION [010]
Enter any value between 001 and 255 to determine the number of seconds
the door may remain open before the Access Alarm is triggered. Default =
60 secs.
3.6.10 Door Left Open Pre-Alarm
SECTION [004]: OPTION [3]
Program the Pre-Alarm timer in section [011].
Option [3] OFF=The Pre-Alarm will not be generated
Option [3] ON=Pre-Alarm is enabled (default)
3.6.11 Door Left Open Pre-Alarm Timer
SECTION [011]
This timer will trigger the Door Left Open Pre-Alarm before the end of the
Door Left Open Interval. Enter any value between 001 and 255 to
determine the seconds before the expiry of the Door Left Open Interval that
the reader will beep. Default = 15 seconds.
3.6.12 Door Left Open Alarm Feedback
SECTION [004]: OPTIONS [5] AND [6]
Option [5] OFF=The Door Left Open Alarm is silent
Option [5] ON=The Door Left Open Alarm is audible (default)
If option [5] is enabled:
Option [6] OFF=Beep as long as the Door Left Open Alarm is
occurring (default)
Option [6] ON=Door Left Open Alarm follows Beep Timer (section [012])
Table 16: Door Unlocked Schedule
Option Day Option Day
[1] Sunday (S) [5] Thursday (T)
[2] Monday (M) [6] Friday (F)
[3] Tuesday (T) [7] Saturday (S)
[4] Wednesday (W) [8] Holidays (H)
Table 17: Door Left Open Access Alarm
Section
[004] Option [3] Door Left Open Pre-alarm
Option [5] Door Left Open Alarm
Option [6] Door Left Open Alarm follows
[010] Door Left Open Interval
[011] Door Left Open Pre-alarm Timer
[012] Beep Timer for Door Left Open Alarm