28 REFERENCE & INSTALLATION MANUAL
Silent alarm
:
The control panel emits a Confirmation Beep and transmits the appropriate Panic report code if programmed in
section [195]. The control panel will not enable the keypad buzzers or the control panel’s BELL output (no audible
alarm).
Audible alarm
:
Same as silent alarm, except the keypad buzzers and the BELL output will activate until a user cancels the alarm
(disarms) with a valid User Access Code or when the Bell Cut-Off Timer elapses (see page 26).
Fire (pulsed) alarm
:
Same as audible operation, except that the BELL output wil l be pulsed as shown in Fi gure 5.3 on page 20.
Whether the system is partitioned or not, the control panel will report all panic alarms to partition 1.
7.5 PANIC LOCKOUT TIMER
Section [094]
When a panic alarm is activated, the control panel can ignore the disarm signal from a remote control (see the SPC-
319 Wireless Bus Module Reference & Installation Manual) for a specified period. This prevents an aggressor from
disarming the system by remote control during a panic situation. In section [094] enter a 3-digit value (000 to 255,
000 = disabled) representing the number of seconds that the remote controls will be locked out of the system.