36 REFERENCE & INSTALLATION MANUAL
8.15 RECENT CLOSE DELAY
Section [0 85 ]
000 to 255 seconds, Default = no delay
If after having armed the system, an alarm is generated within the period defined by the Recent Close Delay, the
control panel will attempt to transmit the Recent Close report code programmed in section [195].
8.16 AUTO TEST REPORT
Sections [087]
000=disabled, 001 to 255 days, Default = disabled
Section [110 ]: Time (HH:M M)
The control panel will transmit the Test Report report code programmed into section [211] after the number of days
programmed into section [087] has elapsed at the time programmed into section [110]. Use the 24-hour clock to
program the time (i.e. 6:30PM = 18:30). The first Test Report will be transmitted within 24 hours after the feature is
enabled at the time programmed in [110].
Example: Section [087] = 005 and section [110] = 13:00. The first Test Report will be sent at 1 PM that day and then
th e report wil l be sen t ever y 5 days at 1 PM.
8.17 POWER FAILURE REPORT DELAY
Section [0 86 ]
001 to 255 minutes, Default = 15 minutes
The control panel will transmit the AC Failure report code programmed in section [205] after the Power Failure
Report Delay period has elapsed.
8.18 DISARM REPORTING OPTIONS
Section [1 31 ]: Arming /Disarming Options
Option [1] OFF = Always Report Disarming
Option [1] ON = Report Disarming Only After Alarm (default)
With option [1] off, the control panel will send the Disarming report codes (see page 30) to the central station every
time the system is disarmed. With option [1] on, the control panel will send the Disarming report codes to the central
station when the system is disarmed following an alarm.
8.19 ZONE RESTORE REPORT OPTIONS
Section [1 32 ]: Zone Option s
Option [6] OFF = Report On Bell Cut-Off (default)
Option [6] ON = Report On Zone Closure
With option [6] off, the control panel wi ll send the Zone Alarm R estore r epor t codes (see page 31) to the central
station when the zone has returned to normal and the Bell Cut-Off Timer has elapsed (see page 26). With option [6]
on, the control panel will send the Zone Alarm Restore report codes to the central station as soon as the zone
returns to normal or when the system is disarmed.
8.20 TELEPHONE LINE MONITORING (TLM)
When enabled, the system verifies the existence of a telephone line once every second. A line test failure occurs
when the TLM detects less than 3 volts for the period defined by the TLM Fail Timer. If the line test fails, the control
panels STATUS LED flashes and generates one or more conditions as defined by the TLM settings below. These will
be restored w hen the control panel detects the tel ephone line agai n. Please note that when the dialer detects an
incoming call, the TLM test will stop for 1 minute.
Section [135 ]: Dialer Options
[1] OFF / [2] OF F: TLM Disabled
[1] OFF / [2] ON : Trouble Only
Upon line test failure, a TLM Trouble will appear in the keypads’ Trouble Display (see page 46).