SPECTRA SERIES 37
[1] ON / [2] OF F: Alarm If System Armed
Upon line test failure, a TLM Trouble will appear in the keypadsTrouble Display (see page 46) and if the system is
armed, the control panel will generate an alarm.
[1] ON / [2] ON : Silent Alarm Becomes Audible
Upon line test failure, a TLM Trouble will appear in the keypadsTrouble Display (see page 46) and causes a silent
zone or si lent panic alarm to switch to audi ble.
8.20.1 TLM FAIL TIMER
Section [079]
016 to 255 x 2 seconds, Default = 32 seconds
If TLM does not detect the existence of a telephone line for the duration of this period, the control panel will
generate the condition(s) defined by the TLM options (see above).
PART 9: PROGRAMMABLE OUTPUTS
A PGM is a programmable output that toggles to its opposite state (i.e. a normally open PGM will close) when a specific event
has occurred in the system. For example, a PGM can be used to reset smoke detectors, activate bells or strobe lights, open/
close garage doors and much more. When a PGM closes, the control panel supplies a ground to the PGM activating any
device or relay connected to it. When a PGM opens, the cir cuit opens from ground, therefore, cutting power to any devices
connected to it.
PGM1
1728EX and 1728 :
A program mable output that provides
up to 150mA
. Re fe r to PGM for 1728EX and 1728 on page 7.
1738EX and 1738 :
A program mable output that provides
up to 1A.
Refer to
Alar m Relay and PGMs for 17 38EX and 1738 on
page 7.
PGM2
1738EX and 1738 only: PGM2 is a programmable output that can provide up to 1A. PGM2 is designed to be used as a
Strobe Output. For information refer to PGM Strobe Options on page 38. For connections, r efer to Alarm Relay and PGMs for
1738EX and 17 38 on page 7.
Global PGM
The Global PGM allows you to use the control panels PGM Event List to activate PGMs located on a module or LCD keypad.
For example, if you enable a module’sFollows Global PGM” option, the PGM on the module will activate whenever the event
programmed in section [124] occurs. Every PGM on every keypad and/or expansion bus module can be programmed to
follow the event(s) defined by the Global PGM.
9.1 PGM ACTIVATION EVENT
Sections [120], [122], and [124]
This feature allows you to program the control panel to activate a PGM when a specific event occurs in the system.
The PGM will remain in its active state until the programmed PGM Deactivation Event occurs or when the PGM
Delay period elapses (see page 38). For the Event List see the PGM Table in the Spectra 1728EX, 1728, 1738EX
and 1738 Programming Guide. PGM2 is available on the 1738EX and 1738 only. To program a PGM Activation
Event:
1) Enter section that represents the desired PGM. PGM1 = [120], PGM2 = [122], Global PGM = [124]
2) Enter the Event Group #.
3) Enter the Sub-Group #.
4) Enter the P art it io n #
01 = Partition 1
02 = Partition 2
99 = Both Partitions
The “AC Loss” PGM Event will only occur after the Power Failure Report Delay elapses (see page 36).