15.1 P
ANEL
I
DENTIFIER
(Default = 0000) The Panel Identifier identifies the control panel to WinLoad
before initiating upload or download. The control panel will verify if the
Panel Identifier in WinLoad is the same. If the codes do not match, the
control panel will not establish communication. Therefore, program the
same Panel Identifier into both the control panel and WinLoad. Enter the
desired 4-digit hexadecimal number into section [3011].
15.2 PC P
ASSWORD
(Default = 0000) The PC Password identifies the computer running the
WinLoad software to the control panel before beginning the download
process. Program the same PC Password into both the control panel and
WinLoad. If the passwords do not match, WinLoad will not establish
communication. Enter the desired four-digit hexadecimal number into
section [3012].
15.3 PC T
ELEPHONE
N
UMBER
The control panel dials this number to communicate with a computer using
WinLoad. Enter any digit from 0 to 9 and any special keys or functions (see
Ta bl e 3, Special Telephone Number Keys, on page 30) up to a maximum of
32 digits into section [3010].
15.4 C
ALL
B
ACK
F
EATURE
(Default = disabled) The Call Back Feature provides additional security.
When option [1] is enabled and a computer using WinLoad attempts to
communicate with the control panel, the control panel hangs up and calls
the computer back to re-verify identification codes and re-establish
communication. When the control panel hangs up, WinLoad automatically
goes into Wait For Call Mode, ready to answer when the control panel calls
back. The PC Telephone Number must be programmed (see section 15.3).
15.5 C
ALL
W
IN
L
OAD
To communicate with WinLoad, press and hold the [0] key, enter the
[
INSTALLER
CODE
] and press [
FORCE
] to dial the PC Telephone Number
programmed in section [3010]. The control panel and WinLoad verify that
the Panel Identifier and the PC Password match before establishing
communication.
15.6 A
NSWER
W
IN
L
OAD
To perform on-site uploading/downloading, connect the computer directly to
the control panel using an ADP-1 line adapter. In WinLoad set Dialing
Condition to Blind Dial. Program the PC telephone number in WinLoad and
follow the ADP-1 Adapters instructions. When the computer has dialed,
press and hold the [0] key, enter the [
INSTALLER
CODE
] and press [
ARM
] to
manually answer WinLoad from the panel. Press [
DISARM
] to hang up.
15.7 A
NSWERING
M
ACHINE
O
VERRIDE
D
ELAY
(Default = 008) If WinLoad will be used to communicate with an installation
that uses an answering machine or service, program the Answering
Machine Override. If the installation is called back within the programmed
delay period, the Answering Machine Override will bypass the answering
machine or service by picking up the line on the first ring. Also, see section
15.8.
In section [3052] program a value (00 to 15 X 4 seconds, 00 = disabled)
representing the delay period the control panel will wait between the first
and second call.
To use:
Step 1: Using WinLoad, call the installation and on the second ring press
the [
ENTER
] key on the keyboard to hang up or hang up manually.
Step 2: After hanging up, WinLoad will immediately call the installation back
or call the site back manually.
For example, an answering machine is set to answer after three rings and
section [3052] is programmed with 10 (10 x 4 = 40 seconds). During the
first call with WinLoad, wait two rings and press [
ENTER
]. WinLoad will
immediately call the site back. If the second call is made within 40 seconds,
the control panel will pick up the line on the first ring. If it takes more than 40
seconds, the control panel will not answer on the first ring and the
answering machine will answer after three rings.
15.8 R
ING
C
OUNTER
(Default = 008) The Ring Counter represents the number of rings the
control panel will wait before picking up the line. If the line is not answered
after the number of programmed rings, the control panel answers the call. If
more than 10 seconds pass between each ring, the Ring Counter resets.
Also, see section 15.7. Enter any value between 01 to 15 (00 = disabled) to
determine the number of rings.
15.9 E
VENT
B
UFFER
T
RANSMISSION
(Default = disabled) Once the Event Buffer contains 1998 events since the
last upload, the control panel makes two attempts to establish
communication with a computer using WinLoad by calling the PC
Telephone Number programmed in section [3010]. WinLoad must be in
Wait To Dial mode. When communication is established, the control panel
uploads the contents of the Event Buffer to WinLoad. If communication is
interrupted before completing transmission or communication is not
established after two attempts, the control panel wait until the Event Buffer
receives another 1998 events before attempting Event Buffer Transmission.
When the Event Buffer is full, each subsequent new event will erase the
oldest event in the buffer. The Event Buffer can hold 2048 Events.